                                            Add to Cart
The test bench is multiple positions up to 3 meters, 0.02% of accuracy class Three-phase Meter Test System with ICTs, with multiple serial port communication system for parallel communication for testing of smart meters.
| Voltage | |
| Test voltage output (Phase-Neutral) | 3×(24 V – 480 V) or 600 V F-F customized | 
| Power of the voltage output | 3×100VA | 
| Resolution | Better than 0.01% of full scale value of range | 
| Setting accuracy | Better than 0.02% at the final range value | 
| Stability | Better than 0.005%/h (integration time 150 s) | 
| Load regulation from 0-max. load | < 0.01% | 
| Distortion factor | < 0.3% for linear resistance load | 
| Harmonics | 2nd – 21st free programmable | 
| Current | |
| Test current output | 0.3 mA – 120 A | 
| Power of the current output | 3×150VA | 
| Resolution | Better than 0.01% of full scale value of range | 
| Setting accuracy | Better than 0.02% at the final range value | 
| Stability | Better than 0.005%/h (integration time 150 s) | 
| Load regulation from 0-max. load | < 0.01% | 
| Distortion factor | < 0.3% for linear resistance load | 
| Harmonics | 2nd – 21st free programmable | 
| Phase angle | |
| Range | 0 -- 360° | 
| Resolution | 0.01° | 
| Setting accuracy | 0.1° | 
| Frequency | |
| Range | 45 Hz – 65 Hz | 
| Resolution | 0.01 Hz | 