Add to Cart
Voltage | 240/415 V AC supply (+5% & -10%) or customized |
Frequency | 50/60Hz ±2Hz |
Power capacity | > 3 × 6kVA |
Ambient temperature | -10°C … +40°C |
Relative humidity | 35% … 95% |
System Grounding | Neutral solidly grounded |
Surge protection level | ≥ 10 kV/120 Joules (10/1000µs) |
Voltage | |
Test voltage output (Phase-Neutral) | 3× (24V – 500V) or customized |
Power of the voltage output | 3×100VA |
Resolution | Better than 0.01% of full scale value of range |
Setting accuracy | Better than 0.05% at the final range value |
Stability | Better than 0.005%/h (integration time 150 s) |
Load regulation from 0-max. load | < 0.01% |
Distortion factor | < 0.3% for linear resistance load |
Harmonics | 2nd – 21st free programmable |
Current | |
Test current output | 3× (1mA – 120A) |
Power of the current output | 3×150VA |
Resolution | Better than 0.01% of full scale value of range |
Setting accuracy | Better than 0.05% at the final range value |
Stability | Better than 0.005%/h (integration time 150 s) |
Load regulation from 0-max. load | < 0.01% |
Distortion factor | < 0.3% for linear resistance load |
Harmonics | 2nd – 21st free programmable |
Phase angle | |
Range | 0 -- 360° |
Resolution | 0.01° |
Setting accuracy | 0.1° |
Frequency | |
Range | 45Hz – 65Hz |
Resolution | 0.01Hz |
Power supply | |
Voltage | AC220V ±10% |
Frequency | 50Hz ±2Hz |
Max power consumption | 45VA |
Using condition | |
Environment temperature | 10ºC … 30ºC |
Relative humidity | 45% … 75% |
Outside magnetic intensity | ≤ 0.025mT |
Frequency range | 45Hz … 65Hz |
Test current | |
Range | 1mA … 120A |
Error | - ±0.02% (50mA…120A) (relative measurement value) - ±0.05% (1…50mA) (relative range full-scale value) |
Current display range | 1.000mA … 120.000A (1A, 10A, 100A) |
Test voltage | |
Range | 50V … 480V (auto range) |
Error | - ±0.02% (50V…480V) (relative measurement value) - ±0.05% (5V…50V) (relative measurement value) |
Voltage display range | 50.000(V) … 480.000(V) |
Power measure error | |
Active power | +0.02% (relative measurement value) 50V … 480V, 0.05A … 120A |
Reactive power | +0.05% (relative measurement value) 50V … 480V, 0.05A … 120A |
Apparent power | +0.05% (relative measurement value) 50V … 480V, 0.05A … 120A |
Test Power Factor(PF=P/F) Error: 0.05% | |
Display range | -1.00000 … +1.00000 |
Energy constant | CH=109 imp/kWh (1A & 0.1A step) CH=108 imp/kWh (10A step) CH=107 imp/kWh (100A step) |
Measuring modes | - 4 wire active/ reactive/ cross-connect reactive - 3 wire active/ reactive/ cross-connect reactive - 2 wire active/ reactive
|
Energy pulse input | |
Frequency | 0.5kHz |
Voltage | 24V |
Measurement range of input | |
Output | TTL pulse, load > 2kΏ |
Dimensions (W * H * D) | 131mm * 432mm * 470mm |
Weight | 16kgs |