Advanced Stationary Meter Test Bench for Comprehensive Electric Parameter Analysis
Features & Functions
- Meters under testing: 1P2W / 3P4W / 3P3W
- Simultaneously measure meters with the same specifications but different meter constants
- Automatic positioning of the rotor mark on the disc of mechanical meters for increased efficiency
- Creeping Test and Starting Test
- Protection against short voltage circuits, overload, and open current circuits
- Constructed from aluminum alloy, lightweight, strong, and corrosion-resistant
- Testing software compatible with Windows XP/7/8/10, includes functional modules for all types of modern energy meters, capable of performing error tests, harmonic tests, demand tests, influence tests, etc.
- High-quality product
- Highest accuracy class: 0.02 / 0.01 (highest level)
- Extremely high power stability
- Influence test for voltage, frequency, and harmonics
- RS232 and Ethernet communication ports installed in each meter position
- Over 18 months warranty, extendable to 36 months for capable units
- Suitable for nation-level utility companies, governmental bureaus of metrology, large energy meter manufacturers, and laboratories for electric energy metering
- The entire system is accredited and conforms to EU health and safety standards with CE certificates
Technical specification for 1~3 position meter test system
The test bench is multiple positions up to 3 meters, 0.02% of accuracy class Three-phase Meter Test System with ICTs, with multiple serial port communication system for parallel communication for testing of smart meters.
Power Supply
| Voltage | 3×240±15% |
| Frequency | 50 Hz ±15% |
| Power capacity | > 6 kVA |
| Power efficient(at full load) | ≥85% |
| Ambient temperature | -10 °C -- +40 °C |
| Relative humidity | 35% -- 85% |
Power Source
| Voltage |
| Test voltage output (Phase-Neutral) | 3×(24 V – 480 V) or 600 V F-F customized |
| Power of the voltage output | 3×100VA |
| Resolution | Better than 0.01% of full scale value of range |
| Setting accuracy | Better than 0.02% at the final range value |
| Stability | Better than 0.005%/h (integration time 150 s) |
| Load regulation from 0-max. load | < 0.01% |
| Distortion factor | < 0.3% for linear resistance load |
| Harmonics | 2nd – 21st free programmable |
| Current |
| Test current output | 0.3 mA – 120 A |
| Power of the current output | 3×150VA |
| Resolution | Better than 0.01% of full scale value of range |
| Setting accuracy | Better than 0.02% at the final range value |
| Stability | Better than 0.005%/h (integration time 150 s) |
| Load regulation from 0-max. load | < 0.01% |
| Distortion factor | < 0.3% for linear resistance load |
| Harmonics | 2nd – 21st free programmable |
| Phase angle |
| Range | 0 -- 360° |
| Resolution | 0.01° |
| Setting accuracy | 0.1° |
| Frequency |
| Range | 45 Hz – 65 Hz |
| Resolution | 0.01 Hz |