Add to Cart
Environment | Safety | |||
Operation Temperature | Relative Humidity | Altitude | IP Class | Conformity |
0℃-40℃ | 40%-95% | <2500m | 40 | IEC |
CT ratio range | 5A/5A~25000A/5A (5A/1A~5000A/1A) Turns ratio error: ±0.2% | |||
Error Measurement Range | 5A/5A~5000A/5A (5A/1A~5000A/1A) | |||
Accuracy range of the inspected current transformer | 1.0, 0.5, 0.5S, 0.2, 0.2S | |||
CT Error Accuracy | 0.02% | |||
PT ratio range | Whole range (electromagnetic type) ±0.2% | |||
Error Measurement Range | Primary Voltage: 3-220kV/√3 (Non-standard primary voltage is ok) | |||
Power factor | 0.0-1.0 | |||
PT error accuracy | 0.05% | |||
DC resistance | 0.0-0.1Ω ±3%, 0.1-50Ω ±1% | |||
Power supply | AC 220V±10%/50Hz±2%, battery (optional) | |||
Power consumption | 30W (static), 150W (working) | |||
Size & Weight | 472mm x 355mm x 168mm, 6.0kg |