Add to Cart
This is a High Accuracy Three Phase Reference Standard Meter, which is suit for Three Phase Energy Meter Test Bench System.
Application Conditions and Requirements | |||||
Environment | Power Requirement | Safety | |||
Operation Temperature | Humidity | Altitude | Voltage Supply | IP Class | Conformity |
-10°ºC--+40ºC | 45%--75% | <2500m | 220V±10%,50/60Hz±2Hz | IP30 | CE conform |
Type | SZ-03A-K8 |
Test voltage | |
Range | 5V-480V |
Error | ±0.02%(5V-480V) |
Display range | 5.000000V-480.000V |
Test current | |
Range | 10mA-120A |
Error | ±0.02%(50mA-120A) ±0.05%(10mA-50mA) |
Display range | 1.000000A-120.0000A |
Power measure error | |
Active power | ±0.02%(50mA-120A) |
Reactive power | ±0.05%(50mA-120A) |
Apparent power | ±0.05%(50mA-120A) |
Phase angle | |
Range | 0°-360° |
Error | ±0.05° |
Display range | 0.000001°--359.9999° |
Frequency | |
Range | 45Hz-65Hz |
Display range | 45.000-65.000 |
Pulse output | |
High frequency output(CH) | 1x109(0A-1A) |
1x108(1A-10A) | |
1x107(10A-120A) | |
Low frequency output(CL) | 2x10-5xCH |
Pulse ratio | 1:1 |
Output level | 5V |
Pulse input | |
Input level | 24V |
Input frequency | 500Hz(Max) |
Dimensions(WxHxD)(mm) | 432x131x470 |
Weight(kg) | 16 |