Guangzhou GENY Electric Co., Ltd

Professional in Energy Meter Testing

Manufacturer from China
Verified Supplier
2 Years
Home / Products / Stationary Meter Test System /

Stationary Meter Test System 24 Positions Energy Meter Tester

Contact Now
Guangzhou GENY Electric Co., Ltd
Visit Website
City:guangzhou
Country/Region:china
Contact Person:MrJohn Shen
Contact Now

Stationary Meter Test System 24 Positions Energy Meter Tester

Ask Latest Price
Video Channel
Brand Name :GENY
Model Number :YC1893D
Certification :ISO, CE
Place of Origin :China
MOQ :1
Price :negotiate rates
Payment Terms :T/T, L/C, D/P, T/T
Supply Ability :5 sets / 1 months
Delivery Time :6~8weeks
Packaging Details :Plywood cases
Accuracy :0.05 / 0.02
Number of meter positions :24
Power Source :YCS-103-1200
Scanning Head :YCG-S Series
Test voltage Output :3x(24V~288V)(or customized)3x(24V~288V)(or customized)
Power of the voltage output :Max 3x500VA
Stability :Better than 0.005% /h
Structure :All-in-one
Usage :Energy Meter Calibration, Lab Research
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

Three Phase Electric Energy Meter Testing Equipment, Fully-Automatic Calibration 24 Meter Position, Accuracy Class 0.02%

Stationary Meter Test System for Three Phase Electric Energy Meters 24 Meter Positions

Specifications:

Technical spec.
Number of meter positions 24
Accuracy 0.05 / 0.02
Power Source YCS-103-1200
Standard Meter SZ03A-K6 / SZ03A-K8
Scanning Head YCG-S Series
Voltage
Test voltage output(Phase-Neutral) 3x(24V~288V)(or customized)
Power of the voltage output Max. 3x500VA
Resolution Better than 0.01% of full scale value of range
Setting accuracy Better than 0.05% at the final range value
Stability Better than 0.005% /h (integration time 150s)
Load regulation from 0~max. load Better than 0.01%
Distortion factor Better than 0.3% for linear resistance load
Harmonic 2nd~21st free programmable
Current
Test current output 3x(1mA~100A)
Power of the current output Max. 3x750VA
Resolution Better than 0.01% of full scale value of range
Setting accuracy Better than 0.05% at the final range value
Stability Better than 0.005% /h (integration time 150s)
Load regulation from 0~max. load Better than 0.01%
Distortion factor Better than 0.3% for linear resistance load
Harmonic 2nd~21st free programmable
Phase angle
Range 0~360⁰
Resolution 0.01⁰
Setting accuracy 0.1⁰
Frequency
Range 45Hz~65Hz
Resolution 0.01Hz
Error display
Type of error display Red LED
Resolution of error displays 8 digitals
Other
Voltage supply

3x220/380V±10%(or customized)

50/60Hz ±2Hz

Ambient temperature -10°C~+40°C
Relative humidity 35%~85%

Description:

1. The meter test system can measure mechanical meter, electronic mechanical meters and electronic meter by ways of automatic, semi-automatic or manual operation.

2. Meters under testing: 3P4W, 3P3W, 1P2W

3. Testing mode: active power, reactive power, cross connected reactive power

4. Simultaneously measure meters with same specifications but different meter constants

5. Automatic positioning rotor mark of disc of mechanical meter, with more efficiency.

6. Starting test and creeping test

7. Neutral current test (optional)

8. Installing the ICT in each meter position to test three-phase meters with closed links between the current and voltage measuring circuits(I-P links)(optional)

9. With the protection function of overload, short voltage circuit and open current circuit.

10. The swing together of the scanning heads simplifies the control.

11. Aluminum alloy material, light and strong and corrosion resistant

12. The testing software with friendly Windows 2000 /XP /7 /8 /10 operation system, includes functional module of all kinds of modern energy meter needed, to reality error test, harmonic test, demand test, influence test etc,.

Applications:

1. Nation-level utility companies

2. Governmental bureaus of metrology

3. Big energy meter manufacturers

Primary Competitive Advantages:

1. High quality product

2. Over 18 months long warranty

3. High accuracy class: 0.05/0.02

4. Can be customized of Three Phase Electric Energy Meter Test bench

5. Extremely high power stability

6. Neutral current test(optional)

7. Timing error test

8. Influence test of voltage, frequency, and harmonic

9. Installing RS232, Ethernet communication port in each meter position.

10. Tilt impact test (optional)

Stationary Meter Test System 24 Positions Energy Meter Tester

Inquiry Cart 0